Generic selectors
Exact matches only
Search in title
Search in content
Post Type Selectors
Generic selectors
Exact matches only
Search in title
Search in content
Post Type Selectors

SCBH17-2500/35 Three-Phase Two-Winding Dry-Type Off-Circuit Tap-Changer Distribution Transformer

35kV Dry-Type Amorphous Alloy Distribution Transformer Series

SCBH17-2500/35 Three-Phase Two-Winding Dry-Type Off-Circuit Tap-Changer Distribution Transformer

The SCBH17-2500/35 is a three-phase, two-winding dry-type distribution transformer with epoxy resin casting, an amorphous alloy core, and an off-circuit tap changer, rated at 2500kVA and 35kV on the high-voltage side. The amorphous alloy core significantly reduces no-load loss compared with conventional silicon steel transformers, delivering substantial energy savings over the transformer’s service life. The transformer features vacuum-cast epoxy resin insulation, providing excellent flame retardancy, moisture resistance, and maintenance-free operation. The amorphous alloy core is made of high-quality ultra-thin alloy strips with a three-frame, three-column structure, and low-voltage windings use copper foil conductors, ensuring low partial discharge, low temperature rise, and strong short-circuit withstand capability. Typical applications include commercial buildings, hospitals, airports, metro stations, data centers, and other indoor locations where fire safety and reliable power supply are essential.
  • Rated Capacity: 2500 kVA
  • Rated Voltage Ratio: 35/0.4 kV
  • Connection Group: Dyn11
  • Cooling Method: AN
  • Energy Efficiency Class: N/A
  • Standard:IEC 60076, GB/T 22072-2018

Product Details

Learn more about our products

Product Model SCBH17-2500/35
No-Load Loss ≤1.332 kW
Rated Capacity 2500 kVA
No-Load Current ≤0.4%
Phase 3-phase
Load Loss (120°C) ≤20.71 kW
Rated Voltage Ratio 35/0.4 kV
Short-Circuit Impedance 6%
HV Tapping Range ±5%
Temperature Rise Limit Winding ≤100K (F-class)
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤65 dB(A)
Connection Group Dyn11
Protection Degree IP20 (IP23 available)
Cooling Method AN
Standard IEC 60076, GB/T 22072-2018
Insulation Class F (155°C), LI170 AC70 / LI75 AC35
Energy Efficiency Class N/A
01.

Core advantages

Ultra-Low No-Load Loss
The amorphous alloy core reduces no-load loss by approximately 60–80% compared with conventional silicon steel transformers, and no-load current by approximately 70–85%. This advantage is most pronounced in continuous light-load applications such as commercial buildings and hospitals, where the transformer operates at low load for extended periods. Actual measured losses are typically lower than reference values, and detailed test data can be provided upon request.
Vacuum-Cast Epoxy Resin
High and low voltage windings are fully impregnated in F-class epoxy resin under vacuum conditions, providing excellent flame retardancy, moisture resistance, and pollution resistance. Partial discharge is typically below 5 pC. The transformer is maintenance-free and suitable for indoor installation, including basements, tunnels, and other enclosed spaces.
Low Noise & Strong Short-Circuit Withstand
Optimized core and winding design delivers low noise operation, suitable for hospitals, schools, and other noise-sensitive locations. The transformer maintains stable operation under continuous load with strong short-circuit withstand capability and a long service life. With forced-air cooling (AF), it can handle short-term overload up to 150% of rated capacity.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

35kV Dry-Type Amorphous Alloy Distribution Transformer Series – Full Specifications

35kV, 3-phase, 2-winding, dry-type,amorphous alloy core,off-circuit tap-changer, distribution transformer, 50-2500kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss (kW)Impedance
Voltage (%)
B(100℃)F(120℃)H(145℃)
SCBH15-50/355033,35,36,37,38.5±5%0.4Dyn110.1501.3401.4201.5206
SCBH17-50/355033,35,36,37,38.5±5%0.4Dyn110.1351.2731.3491.4446
SCBH19-50/355033,35,36,37,38.5±5%0.4Dyn110.1351.2061.2781.3686
SCBH15-100/3510033,35,36,37,38.5±5%0.4Dyn110.2001.9702.0902.2306
SCBH17-100/3510033,35,36,37,38.5±5%0.4Dyn110.1801.8721.9862.1196
SCBH19-100/3510033,35,36,37,38.5±5%0.4Dyn110.1801.7731.8812.0076
SCBH15-160/3516033,35,36,37,38.5±5%0.4Dyn110.2402.6502.8103.0006
SCBH17-160/3516033,35,36,37,38.5±5%0.4Dyn110.2162.5182.6702.8506
SCBH19-160/3516033,35,36,37,38.5±5%0.4Dyn110.2162.3852.5292.7006
SCBH15-200/3520033,35,36,37,38.5±5%0.4Dyn110.2803.1303.3203.5506
SCBH17-200/3520033,35,36,37,38.5±5%0.4Dyn110.2522.9743.1542.3736
SCBH19-200/3520033,35,36,37,38.5±5%0.4Dyn110.2522.8172.9883.1956
SCBH15-250/3525033,35,36,37,38.5±5%0.4Dyn110.3103.5803.8004.0606
SCBH17-250/3525033,35,36,37,38.5±5%0.4Dyn110.2793.4013.6103.8576
SCBH19-250/3525033,35,36,37,38.5±5%0.4Dyn110.2793.2223.4203.6546
SCBH15-315/3531533,35,36,37,38.5±5%0.4Dyn110.3704.2504.5104.8206
SCBH17-315/3531533,35,36,37,38.5±5%0.4Dyn110.3334.0384.2854.5796
SCBH19-315/3531533,35,36,37,38.5±5%0.4Dyn110.3333.8254.0594.3386
SCBH15-400/3540033,35,36,37,38.5±5%0.4Dyn110.4305.1005.4105.7906
SCBH17-400/3540033,35,36,37,38.5±5%0.4Dyn110.3874.8455.1405.5016
SCBH19-400/3540033,35,36,37,38.5±5%0.4Dyn110.3874.5904.8695.2116
SCBH15-500/3550033,35,36,37,38.5±5%0.4Dyn110.5006.2706.6507.1106
SCBH17-500/3550033,35,36,37,38.5±5%0.4Dyn110.4505.9576.3186.7556
SCBH19-500/3550033,35,36,37,38.5±5%0.4Dyn110.4505.6435.9856.3996
SCBH15-630/3563033,35,36,37,38.5±5%0.4Dyn110.5807.2507.6908.2306
SCBH17-630/3563033,35,36,37,38.5±5%0.4Dyn110.5226.8887.3067.8196
SCBH19-630/3563033,35,36,37,38.5±5%0.4Dyn110.5226.5256.9217.4076
SCBH15-800/3580033,35,36,37,38.5±5%0.4Dyn110.6808.6009.1209.7606
SCBH17-800/3580033,35,36,37,38.5±5%0.4Dyn110.6128.1708.6649.2726
SCBH19-800/3580033,35,36,37,38.5±5%0.4Dyn110.6127.7408.2088.7846
SCBH15-1000/35100033,35,36,37,38.5±5%0.4Dyn110.7509.86010.40011.1006
SCBH17-1000/35100033,35,36,37,38.5±5%0.4Dyn110.6759.3679.88010.5456
SCBH19-1000/35100033,35,36,37,38.5±5%0.4Dyn110.6758.8749.3609.9906
SCBH15-1250/35125033,35,36,37,38.5±5%0.4Dyn110.88012.00012.70013.6006
SCBH17-1250/35125033,35,36,37,38.5±5%0.4Dyn110.79211.40012.06512.9206
SCBH19-1250/35125033,35,36,37,38.5±5%0.4Dyn110.79210.80011.43012.2406
SCBH15-1600/35160033,35,36,37,38.5±5%0.4Dyn111.00014.60015.40016.5006
SCBH17-1600/35160033,35,36,37,38.5±5%0.4Dyn110.90013.87014.63015.6756
SCBH19-1600/35160033,35,36,37,38.5±5%0.4Dyn110.90013.14013.86014.8506
SCBH15-2000/35200033,35,36,37,38.5±5%0.4Dyn111.25017.20018.20019.5006
SCBH17-2000/35200033,35,36,37,38.5±5%0.4Dyn111.12516.34017.29018.5256
SCBH19-2000/35200033,35,36,37,38.5±5%0.4Dyn111.12515.48016.38017.5506
SCBH15-2500/35250033,35,36,37,38.5±5%0.4Dyn111.48020.60021.80023.3006
SCBH17-2500/35250033,35,36,37,38.5±5%0.4Dyn111.33219.57020.71022.1356
SCBH19-2500/35250033,35,36,37,38.5±5%0.4Dyn111.33218.54019.62020.9706
SCBH15-1600/35160033,35,36,37,38.5±5%0.4Dyn111.00016.00017.00018.2008
SCBH17-1600/35160033,35,36,37,38.5±5%0.4Dyn110.90015.20016.15017.2908
SCBH19-1600/35160033,35,36,37,38.5±5%0.4Dyn110.90014.40015.30016.3808
SCBH15-2000/35200033,35,36,37,38.5±5%0.4Dyn111.25019.00020.10021.5008
SCBH17-2000/35200033,35,36,37,38.5±5%0.4Dyn111.12518.05019.09520.4258
SCBH19-2000/35200033,35,36,37,38.5±5%0.4Dyn111.12517.10018.09019.3508
SCBH15-2500/35250033,35,36,37,38.5±5%0.4Dyn111.48022.70024.00025.7008
SCBH17-2500/35250033,35,36,37,38.5±5%0.4Dyn111.33221.56522.80024.4158
SCBH19-2500/35250033,35,36,37,38.5±5%0.4Dyn111.33220.43021.60023.1308
Note:
1.Tapping range options: ±5% or ±2×2.5%. ±5% is shown as default in this table. Other tapping ranges are available upon request.
2.Other high and low voltages are available upon request.
3.Vector group options: Dyn11 or Yyn0. Other vector groups are available upon request.
4.Insulation class: B/F/H available. Load losses are shown for reference temperatures of 100°C (Class B), 120°C (Class F), and 145°C (Class H) respectively.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.

* For specific product requests, please Contact Us for customized solutions to your needs.

Contact information

Leave your contact information to download documents

Contact us

Please complete the form below to access and download our file resources.