SCB18-630/20 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Distribution Transformer

20kV Dry-Type Distribution Transformer Series

SCB18-630/20 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Distribution Transformer

The SCB18-630/20 is a three-phase, two-winding dry-type distribution transformer with epoxy resin casting and an off-circuit tap changer, rated at 630kVA and 20kV on the high-voltage side. It is designed for indoor applications where fire safety, moisture resistance, and maintenance-free operation are essential. The transformer features vacuum-cast epoxy resin insulation, providing excellent flame retardancy and pollution resistance. The core is made of high-quality cold-rolled grain-oriented silicon steel, and low-voltage windings use copper foil conductors, ensuring low partial discharge, low temperature rise, and strong short-circuit withstand capability. Typical applications include commercial buildings, hospitals, airports, metro stations, data centers, and other indoor locations where fire safety and high energy efficiency are essential.
  • Rated Capacity: 630 kVA
  • Rated Voltage Ratio: 20/0.4 kV
  • Connection Group: Dyn11
  • Cooling Method: AN
  • Energy Efficiency Class: N/A
  • Standard:IEC 60076, GB/T 10228-2023

Product Details

Learn more about our products

Product Model SCB18-630/20
No-Load Loss ≤1.028 kW
Rated Capacity 630 kVA
No-Load Current ≤0.9%
Phase 3-phase
Load Loss (120°C) ≤6.156 kW
Rated Voltage Ratio 20/0.4 kV
Short-Circuit Impedance 6%
HV Tapping Range ±2×2.5%
Temperature Rise Limit Winding ≤100K (F-class)
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤55 dB(A)
Connection Group Dyn11 (Yyn0 available upon request)
Protection Degree IP20 (IP23 available)
Cooling Method AN
Standard IEC 60076, GB/T 10228-2023
Insulation Class F (155°C), LI125 AC50 / AC5
Energy Efficiency Class N/A
01.

Core advantages

High Energy Efficiency Design (SCB18 Level)
Designed with SCB18-level low-loss core and winding. Compared with conventional models, no-load loss is significantly reduced, delivering substantial energy savings over the transformer's service life, especially for continuous light-load applications such as data centers and commercial buildings. Actual measured losses are typically lower than the standard limits, and detailed test data can be provided upon request.
Vacuum-Cast Epoxy Resin
High and low voltage windings are fully impregnated in F-class epoxy resin under vacuum conditions, providing excellent flame retardancy, moisture resistance, and pollution resistance. The transformer is maintenance-free and suitable for indoor installation, including basements, tunnels, and other enclosed spaces.
Low Partial Discharge & Strong Short-Circuit Withstand
Optimized insulation structure and copper foil low-voltage windings ensure low partial discharge and strong short-circuit withstand capability. The transformer maintains stable operation under continuous load with a long service life.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

20kV Dry-Type Distribution Transformer Series – Full Specifications

20kV, 3-phase, 2-winding, dry-type, off-circuit tap-changer, distribution transformer, 50-2500kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss (kW)Impedance
Voltage (%)
B(100℃)F(120℃)H(145℃)
SCB18-50/205020,22,24±5%0.4Dyn11,Yyn00.2291.0441.1071.1796
SCB14-50/205020,22,24±5%0.4Dyn11,Yyn00.2591.0441.1071.1796
SCB12-50/205020,22,24±5%0.4Dyn11,Yyn00.2751.1601.2301.3106
SCB18-100/2010020,22,24±5%0.4Dyn11,Yyn00.3641.6831.7911.9176
SCB14-100/2010020,22,24±5%0.4Dyn11,Yyn00.4121.6831.7911.9176
SCB12-100/2010020,22,24±5%0.4Dyn11,Yyn00.4371.8701.9902.1306
SCB18-160/2016020,22,24±5%0.4Dyn11,Yyn00.4502.0972.2232.3766
SCB14-160/2016020,22,24±5%0.4Dyn11,Yyn00.5102.0972.2232.3766
SCB12-160/2016020,22,24±5%0.4Dyn11,Yyn00.5402.3302.4702.6406
SCB18-200/2020020,22,24±5%0.4Dyn11,Yyn00.4912.4932.6462.8266
SCB14-200/2020020,22,24±5%0.4Dyn11,Yyn00.5572.4932.6462.8266
SCB12-200/2020020,22,24±5%0.4Dyn11,Yyn00.5902.7702.9403.1406
SCB18-250/2025020,22,24±5%0.4Dyn11,Yyn00.5662.8983.0783.2946
SCB14-250/2025020,22,24±5%0.4Dyn11,Yyn00.6422.8983.0783.2946
SCB12-250/2025020,22,24±5%0.4Dyn11,Yyn00.6803.2203.4203.6606
SCB18-315/2031520,22,24±5%0.4Dyn11,Yyn00.6533.4653.6723.9246
SCB14-315/2031520,22,24±5%0.4Dyn11,Yyn00.7403.4653.6723.9246
SCB12-315/2031520,22,24±5%0.4Dyn11,Yyn00.7833.8504.0804.3606
SCB18-400/2040020,22,24±5%0.4Dyn11,Yyn00.7734.1854.3564.6626
SCB14-400/2040020,22,24±5%0.4Dyn11,Yyn00.8764.1854.3564.6626
SCB12-400/2040020,22,24±5%0.4Dyn11,Yyn00.9274.6504.8405.1806
SCB18-500/2050020,22,24±5%0.4Dyn11,Yyn00.9084.9145.2115.5716
SCB14-500/2050020,22,24±5%0.4Dyn11,Yyn01.0294.9145.2115.5716
SCB12-500/2050020,22,24±5%0.4Dyn11,Yyn01.0895.4605.7906.1906
SCB18-630/2063020,22,24±5%0.4Dyn11,Yyn01.0285.8056.1566.5886
SCB14-630/2063020,22,24±5%0.4Dyn11,Yyn01.1655.8056.1566.5886
SCB12-630/2063020,22,24±5%0.4Dyn11,Yyn01.2336.4506.8407.3206
SCB18-800/2080020,22,24±5%0.4Dyn11,Yyn01.1787.0117.4347.9566
SCB14-800/2080020,22,24±5%0.4Dyn11,Yyn01.3357.0117.4347.9566
SCB12-800/2080020,22,24±5%0.4Dyn11,Yyn01.4137.7908.2608.8406
SCB18-1000/20100020,22,24±5%0.4Dyn11,Yyn01.3958.2988.8029.3606
SCB14-1000/20100020,22,24±5%0.4Dyn11,Yyn01.5818.2988.8029.3606
SCB12-1000/20100020,22,24±5%0.4Dyn11,Yyn01.6749.2209.78010.4006
SCB18-1250/20125020,22,24±5%0.4Dyn11,Yyn01.6059.72010.35011.0706
SCB14-1250/20125020,22,24±5%0.4Dyn11,Yyn01.8199.72010.35011.0706
SCB12-1250/20125020,22,24±5%0.4Dyn11,Yyn01.92610.80011.50012.3006
SCB18-1600/20160020,22,24±5%0.4Dyn11,Yyn01.88311.70012.42013.3206
SCB14-1600/20160020,22,24±5%0.4Dyn11,Yyn02.13411.70012.42013.3206
SCB12-1600/20160020,22,24±5%0.4Dyn11,Yyn02.25913.00013.80014.8006
SCB18-2000/20200020,22,24±5%0.4Dyn11,Yyn02.18313.86014.67015.7506
SCB14-2000/20200020,22,24±5%0.4Dyn11,Yyn02.47413.86014.67015.7506
SCB12-2000/20200020,22,24±5%0.4Dyn11,Yyn02.61915.40016.30017.5006
SCB18-2500/20250020,22,24±5%0.4Dyn11,Yyn02.61016.38017.37018.6306
SCB14-2500/20250020,22,24±5%0.4Dyn11,Yyn02.95816.38017.37018.6306
SCB12-2500/20250020,22,24±5%0.4Dyn11,Yyn03.13218.20019.30020.7006
Note:
1.Tapping range options: ±5% or ±2×2.5%. ±5% is shown as default in this table. Other tapping ranges are available upon request.
2.Other high and low voltages are available upon request.
3.Vector group options: Dyn11 or Yyn0. Other vector groups are available upon request.
4.Insulation class: B/F/H available. Load losses are shown for reference temperatures of 100°C (Class B), 120°C (Class F), and 145°C (Class H) respectively.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.

* For specific product requests, please Contact Us for customized solutions to your needs.

Contact information

Leave your contact information to download documents

Contact us

Please complete the form below to access and download our file resources.