SCB18-3150/35 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Power Transformer

35kV Dry-Type Power Transformer Series

SCB18-3150/35 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Power Transformer

The SCB18-3150/35 is a three-phase, two-winding dry-type power transformer with epoxy resin casting and an off-circuit tap changer, rated at 3150kVA and 35kV on the high-voltage side. It is designed for indoor applications where fire safety, moisture resistance, and maintenance-free operation are essential. The transformer features vacuum-cast epoxy resin insulation, providing excellent flame retardancy and pollution resistance. The core is made of high-quality cold-rolled grain-oriented silicon steel, and low-voltage windings use copper foil conductors, ensuring low partial discharge, low temperature rise, and strong short-circuit withstand capability. Typical applications include industrial facilities, commercial buildings, data centers, substations, and other indoor locations where fire safety and reliable power supply are essential.
  • Rated Capacity: 3150 kVA
  • Rated Voltage Ratio: 35/10.5 kV
  • Connection Group: Dyn11
  • Cooling Method: AN
  • Energy Efficiency Class: N/A
  • Standard:IEC 60076, GB/T 10228-2023

Product Details

Learn more about our products

Product Model SCB18-3150/35
No-Load Loss ≤4.065 kW
Rated Capacity 3150 kVA
No-Load Current ≤0.6%
Phase 3-phase
Load Loss (120°C) ≤22.05 kW
Rated Voltage Ratio 35/10.5 kV
Short-Circuit Impedance 8%
HV Tapping Range ±2×2.5%
Temperature Rise Limit Winding ≤100K (F-class)
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤65 dB(A)
Connection Group Dyn11
Protection Degree IP20 (IP23 available)
Cooling Method AN
Standard IEC 60076, GB/T 10228-2023
Insulation Class F (155°C), LI170 AC70 / LI75 AC35
Energy Efficiency Class N/A
01.

Core advantages

Low Loss Design (SCB18 Level)
Designed with SCB18-level low-loss core and winding. Compared with conventional models, no-load loss is significantly reduced, delivering energy savings over the transformer's service life, especially for continuous light-load applications such as data centers and commercial buildings. Actual measured losses are typically lower than reference values, and detailed test data can be provided upon request.
Vacuum-Cast Epoxy Resin
High and low voltage windings are fully impregnated in F-class epoxy resin under vacuum conditions, providing excellent flame retardancy, moisture resistance, and pollution resistance. The transformer is maintenance-free and suitable for indoor installation, including basements, tunnels, and other enclosed spaces.
Low Partial Discharge & Strong Short-Circuit Withstand
Optimized insulation structure and copper foil low-voltage windings ensure low partial discharge and strong short-circuit withstand capability. The transformer maintains stable operation under continuous load with a long service life.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

35kV Dry-Type Power Transformer Series – Full Specifications

35kV, 3-phase, 2-winding, dry-type, off-circuit tap-changer, power transformer, 800-25000kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss (kW)Impedance
Voltage (%)
B(100℃)F(120℃)H(145℃)
SCB18-800/3580035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn01.5157.9838.4609.0006
SCB14-800/3580035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn01.7177.9838.4609.0006
SCB12-800/3580035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn01.8188.8709.40010.0006
SCB18-1000/35100035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn01.8009.2709.81010.4406
SCB14-1000/35100035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.0409.2709.81010.4406
SCB12-1000/35100035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.16010.30010.90011.6006
SCB18-1250/35125035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.10810.89011.61012.4206
SCB14-1250/35125035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.38910.89011.61012.4206
SCB12-1250/35125035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.52912.10012.90013.8006
SCB18-1600/35160035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.49013.14013.86014.8506
SCB14-1600/35160035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.82213.14013.86014.8506
SCB12-1600/35160035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.98814.60015.40016.5006
SCB18-2000/35200035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn02.85015.48016.38017.5507
SCB14-2000/35200035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn03.23015.48016.38017.5507
SCB12-2000/35200035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn03.42017.20018.20019.5007
SCB18-2500/35250035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn03.27818.54019.62020.9707
SCB14-2500/35250035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn03.71518.54019.62020.9707
SCB12-2500/35250035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn03.93320.60021.80023.3007
SCB18-3150/35315035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn04.06520.79022.05023.5808
SCB14-3150/35315035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn04.60720.79022.05023.5808
SCB12-3150/35315035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn04.87823.10024.50026.2008
SCB18-4000/35400035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn04.73324.93026.46028.3508
SCB14-4000/35400035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn05.36424.93026.46028.3508
SCB12-4000/35400035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn05.67927.70029.40031.5008
SCB18-5000/35500035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn024.67529.61031.41033.6608
SCB14-5000/35500035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn027.96529.61031.41033.6608
SCB12-5000/35500035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn029.61032.90034.90037.4008
SCB18-6300/35630035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn06.68334.65036.72039.3308
SCB14-6300/35630035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn07.57434.65036.72039.3308
SCB12-6300/35630035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,Yyn08.01938.50040.80043.7008
SCB18-8000/35800035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd117.57539.06041.40044.3709
SCB14-8000/35800035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd118.58539.06041.40044.3709
SCB12-8000/35800035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd119.09043.40046.00049.3009
SCB18-10000/351000035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd118.70047.16049.95053.4609
SCB14-10000/351000035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd119.86047.16049.95053.4609
SCB12-10000/351000035,36,37,38.5±5%3.15,6,6.3,10,10.5,11Dyn11,Yd11,YNd1110.44052.40055.50059.4009
SCB18-12500/351250035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1110.57554.81058.14062.1909
SCB14-12500/351250035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1111.98554.81058.14062.1909
SCB12-12500/351250035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1112.69060.90064.60069.1009
SCB18-16000/351600035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1112.97564.53068.40073.1709
SCB14-16000/351600035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1114.70564.53068.40073.1709
SCB12-16000/351600035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1115.57071.70076.00081.3009
SCB18-20000/352000035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1115.45072.54076.95082.35010
SCB16-20000/352000035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1117.51072.54076.95082.35010
SCB12-20000/352000035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1118.54080.60085.50091.50010
SCB18-25000/352500035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1118.22585.77090.90097.20010
SCB16-25000/352500035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1120.65585.77090.90097.20010
SCB12-25000/352500035,36,37,38.5±5%6,6.3,10,10.5,11Dyn11,Yd11,YNd1121.87095.300101.000108.00010
Note:
1.Tapping range options: ±5% or ±2×2.5%. ±5% is shown as default in this table. Other tapping ranges are available upon request.
2.Other high and low voltages are available upon request.
3.Other vector groups are available upon request.
4.Insulation class: B/F/H available. Load losses are shown for reference temperatures of 100°C (Class B), 120°C (Class F), and 145°C (Class H) respectively.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.

* For specific product requests, please Contact Us for customized solutions to your needs.

Contact information

Leave your contact information to download documents

Contact us

Please complete the form below to access and download our file resources.