SCB18-1000/10-NX1 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Distribution Transformer

10kV Dry-Type Distribution Transformer Series

SCB18-1000/10-NX1 Three-Phase Two-Winding Dry-Type Air-Cooled Off-Circuit Tap-Changer Distribution Transformer

The SCB18-1000/10-NX1 is a three-phase, two-winding dry-type distribution transformer with epoxy resin casting and an off-circuit tap changer, rated at 1000kVA and 10kV on the high-voltage side. Designed to meet Class 1 energy efficiency (NX1) under GB 20052-2024, its actual no-load and load losses are typically lower than the standard limits, depending on design and manufacturing. Detailed test data can be provided upon request. The transformer features vacuum-cast epoxy resin insulation, offering excellent flame retardancy, moisture resistance, and maintenance-free operation. The core is made of high-quality cold-rolled grain-oriented silicon steel, and windings use oxygen-free copper conductors, ensuring low partial discharge, low temperature rise, and strong short-circuit withstand capability. Typical applications include commercial buildings, hospitals, airports, metro stations, data centers, and other indoor locations where fire safety and high energy efficiency are essential.
  • Rated Capacity: 1000 kVA
  • Rated Voltage Ratio: 10/0.4 kV
  • Connection Group: Dyn11
  • Cooling Method: AN
  • Energy Efficiency Class: NX1
  • Standard:IEC 60076, GB/T 10228-2023

Product Details

Learn more about our products

Product Model SCB18-1000/10-NX1
No-Load Loss ≤1.02 kW
Rated Capacity 1000 kVA
No-Load Current ≤0.7%
Phase 3-phase
Load Loss (120°C) ≤7.315 kW
Rated Voltage Ratio 10/0.4 kV
Short-Circuit Impedance 6%
HV Tapping Range ±5%
Temperature Rise Limit Winding ≤100K (F-class)
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤55 dB(A)
Connection Group Dyn11 (Yyn0 available upon request)
Protection Degree IP20 (IP23 available)
Cooling Method AN
Standard IEC 60076, GB/T 10228-2023
Insulation Class F (155°C), LI75 AC28 / AC5
Energy Efficiency Class NX1
01.

Core advantages

Class 1 Energy Efficiency (NX1)
Complies with GB 20052-2024 Class 1 energy efficiency standard. Compared with SCB14, no-load loss is reduced by approximately 15%, delivering significant energy savings over the transformer's service life, especially for continuous light-load applications such as data centers and commercial buildings
Vacuum-Cast Epoxy Resin
High and low voltage windings are fully impregnated in F-class epoxy resin under vacuum conditions, providing excellent flame retardancy, moisture resistance, and pollution resistance. The transformer is maintenance-free and suitable for indoor installation, including basements, tunnels, and other enclosed spaces
Low Partial Discharge & Low Temperature Rise
Optimized insulation structure and foil-wound windings ensure low partial discharge and low temperature rise. The transformer maintains stable operation under continuous load, with strong short-circuit withstand capability and long service life.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

10kV Dry-Type Distribution Transformer Series – Full Specifications

10kV, 3-phase, 2-winding, dry-type, off-circuit tap-changer, distribution transformer, 30-2500kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss (kW)Impedance
Voltage (%)
B(100℃)F(120℃)H(145℃)
SCB18-30/10-NX13010,10.5,11±5%0.4Dyn11,Yyn00.1050.6050.6400.6854
SCB14-30/10-NX23010,10.5,11±5%0.4Dyn11,Yyn00.1300.6050.6400.6854
SCB12-30/10-NX33010,10.5,11±5%0.4Dyn11,Yyn00.1500.6700.7100.7604
SCB18-50/10-NX15010,10.5,11±5%0.4Dyn11,Yyn00.1550.8450.9000.9654
SCB14-50/10-NX25010,10.5,11±5%0.4Dyn11,Yyn00.1850.8450.9000.9654
SCB12-50/10-NX35010,10.5,11±5%0.4Dyn11,Yyn00.2150.9401.0001.0704
SCB18-80/10-NX18010,10.5,11±5%0.4Dyn11,Yyn00.2101.1601.2401.3304
SCB14-80/10-NX28010,10.5,11±5%0.4Dyn11,Yyn00.2501.1601.2401.3304
SCB12-80/10-NX38010,10.5,11±5%0.4Dyn11,Yyn00.2951.2901.3801.4804
SCB18-100/10-NX110010,10.5,11±5%0.4Dyn11,Yyn00.2301.3301.4151.5204
SCB14-100/10-NX210010,10.5,11±5%0.4Dyn11,Yyn00.2701.3301.4151.5204
SCB12-100/10-NX310010,10.5,11±5%0.4Dyn11,Yyn00.3201.4801.5701.6904
SCB18-125/10-NX112510,10.5,11±5%0.4Dyn11,Yyn00.2701.5651.6651.7804
SCB14-125/10-NX212510,10.5,11±5%0.4Dyn11,Yyn00.3201.5651.6651.7804
SCB12-125/10-NX312510,10.5,11±5%0.4Dyn11,Yyn00.3751.7401.8501.9804
SCB18-160/10-NX116010,10.5,11±5%0.4Dyn11,Yyn00.3101.8001.9152.0504
SCB14-160/10-NX216010,10.5,11±5%0.4Dyn11,Yyn00.3651.8001.9152.0504
SCB12-160/10-NX316010,10.5,11±5%0.4Dyn11,Yyn00.4302.0002.1302.2804
SCB18-200/10-NX120010,10.5,11±5%0.4Dyn11,Yyn00.3602.1352.2752.4404
SCB14-200/10-NX220010,10.5,11±5%0.4Dyn11,Yyn00.4202.1352.2752.4404
SCB12-200/10-NX320010,10.5,11±5%0.4Dyn11,Yyn00.4952.3702.5302.7104
SCB18-250/10-NX125010,10.5,11±5%0.4Dyn11,Yyn00.4152.3302.4852.6654
SCB14-250/10-NX225010,10.5,11±5%0.4Dyn11,Yyn00.4902.3302.4852.6654
SCB12-250/10-NX325010,10.5,11±5%0.4Dyn11,Yyn00.5752.5902.7602.9604
SCB18-315/10-NX131510,10.5,11±5%0.4Dyn11,Yyn00.5102.9453.1253.3554
SCB14-315/10-NX231510,10.5,11±5%0.4Dyn11,Yyn00.6002.9453.1253.3554
SCB12-315/10-NX331510,10.5,11±5%0.4Dyn11,Yyn00.7053.2703.4703.7304
SCB18-400/10-NX140010,10.5,11±5%0.4Dyn11,Yyn00.5703.3753.5903.8504
SCB14-400/10-NX240010,10.5,11±5%0.4Dyn11,Yyn00.6653.3753.5903.8504
SCB12-400/10-NX340010,10.5,11±5%0.4Dyn11,Yyn00.7853.7503.9904.2804
SCB18-500/10-NX150010,10.5,11±5%0.4Dyn11,Yyn00.6704.1304.3904.7054
SCB14-500/10-NX250010,10.5,11±5%0.4Dyn11,Yyn00.7904.1304.3904.7054
SCB12-500/10-NX350010,10.5,11±5%0.4Dyn11,Yyn00.9304.5904.8805.2304
SCB18-630/10-NX163010,10.5,11±5%0.4Dyn11,Yyn00.7754.9755.2905.6604
SCB14-630/10-NX263010,10.5,11±5%0.4Dyn11,Yyn00.9104.9755.2905.6604
SCB12-630/10-NX363010,10.5,11±5%0.4Dyn11,Yyn01.0705.5305.8806.2904
SCB18-800/10-NX180010,10.5,11±5%0.4Dyn11,Yyn00.8755.8956.2656.7156~8
SCB14-800/10-NX280010,10.5,11±5%0.4Dyn11,Yyn01.0355.8956.2656.7156~8
SCB12-800/10-NX380010,10.5,11±5%0.4Dyn11,Yyn01.2156.5506.9607.4606~8
SCB18-1000/10-NX1100010,10.5,11±5%0.4Dyn11,Yyn01.0206.8857.3157.8856~8
SCB14-1000/10-NX2100010,10.5,11±5%0.4Dyn11,Yyn01.2056.8857.3157.8856~8
SCB12-1000/10-NX3100010,10.5,11±5%0.4Dyn11,Yyn01.4157.6508.1308.7606~8
SCB18-1250/10-NX1125010,10.5,11±5%0.4Dyn11,Yyn01.2058.1908.7209.3356~8
SCB14-1250/10-NX2125010,10.5,11±5%0.4Dyn11,Yyn01.4208.1908.7209.3356~8
SCB12-1250/10-NX3125010,10.5,11±5%0.4Dyn11,Yyn01.6709.1009.69010.3706~8
SCB18-1600/10-NX1160010,10.5,11±5%0.4Dyn11,Yyn01.4159.94510.55511.3206~8
SCB14-1600/10-NX2160010,10.5,11±5%0.4Dyn11,Yyn01.3359.94510.55511.3206~8
SCB12-1600/10-NX3160010,10.5,11±5%0.4Dyn11,Yyn01.96011.05011.73012.5806~8
SCB18-2000/10-NX1200010,10.5,11±5%0.4Dyn11,Yyn01.76012.24013.00514.0056~8
SCB14-2000/10-NX2200010,10.5,11±5%0.4Dyn11,Yyn02.07512.24013.00514.0056~8
SCB12-2000/10-NX3200010,10.5,11±5%0.4Dyn11,Yyn02.44013.60014.45015.5606~8
SCB18-2500/10-NX1250010,10.5,11±5%0.4Dyn11,Yyn02.08014.53515.44516.6056~8
SCB14-2500/10-NX2250010,10.5,11±5%0.4Dyn11,Yyn02.45014.53515.44516.6056~8
SCB12-2500/10-NX3250010,10.5,11±5%0.4Dyn11,Yyn02.88016.15017.17018.4506~8
Note:
1.Tapping range options: ±5% or ±2×2.5%. ±5% is shown as default in this table. Other tapping ranges are available upon request.
2.Other high and low voltages are available upon request.
3.Vector group options: Dyn11 or Yyn0. Other vector groups are available upon request.
4.Insulation class: B/F/H available. Load losses are shown for reference temperatures of 100°C (Class B), 120°C (Class F), and 145°C (Class H) respectively.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.

* For specific product requests, please Contact Us for customized solutions to your needs.