S22-M-10000/35-NX1 Three-Phase Two-Winding Oil-Immersed Off-Circuit Tap-Changer Renewable Energy Transformer

35kV Oil-Immersed Renewable Energy Transformer Series

S22-M-10000/35-NX1 Three-Phase Two-Winding Oil-Immersed Off-Circuit Tap-Changer Renewable Energy Transformer

The S22-M-10000/35-NX1 is a three-phase, two-winding oil-immersed power transformer with a fully sealed corrugated tank and an off-circuit tap changer, rated at 10000kVA and 35kV on the high-voltage side. Designed to meet Class 1 energy efficiency (NX1) under GB 20052-2024, it delivers exceptionally low no-load loss, making it a leading choice for large industrial bases, commercial centers, and urban grid upgrades. The transformer features a fully sealed corrugated tank structure that isolates the oil from air, slowing insulation aging and enabling maintenance-free operation. The core uses high-quality cold-rolled grain-oriented silicon steel, and windings use oxygen-free copper conductors, ensuring low partial discharge, low temperature rise, and strong short-circuit withstand capability for continuous heavy-load operation.
  • Rated Capacity: 10000 kVA
  • Rated Voltage Ratio: 35~38.5 / 0.4-1.14 kV
  • Connection Group: Yd11
  • Cooling Method: ONAN
  • Energy Efficiency Class: NX1
  • Standard:IEC 60076, GB 20052-2024

Product Details

Learn more about our products

Product Model S22-M-10000/35-NX1
No-Load Loss ≤4.8 kW
Rated Capacity 10000 kVA
No-Load Current ≤0.28%
Phase Three-phase
Load Loss (120°C) ≤40.8kW
Rated Voltage Ratio 35~38.5/0.4~1.14 kV
Short-Circuit Impedance 6~14%
HV Tapping Range ±2×2.5%
Temperature Rise Limit Top oil ≤55K, Winding ≤65K
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤65 dB(A)
Connection Group Yd11
Protection Degree IP55
Cooling Method ONAN
Standard IEC 60076, GB 20052-2024
Insulation Class A, LI200 AC85 / AC5
Energy Efficiency Class NX1
01.

Core advantages

Class 1 Energy Efficiency (NX1)
Complies with GB 20052-2024 Class 1 energy efficiency standard. Compared with lower efficiency grades, the transformer delivers exceptionally low no-load loss, ensuring minimum lifecycle cost for continuous heavy-load applications. For large industrial bases and urban grids that operate year-round, the energy savings over the service life are substantial. Actual measured losses are typically lower than the standard limits; detailed test reports are available upon request
Fully Sealed & Low Maintenance
Fully sealed corrugated tank with vacuum oil filling isolates oil from air, preventing oxidation and moisture ingress. This design requires no routine oil-level checks or silica gel replacement, effectively reducing O&M costs for large, continuously operating facilities.
Strong Short-Circuit Withstand for Continuous Heavy Load
Optimized core and winding support structure provide strong short-circuit resistance, suitable for the heavy and continuous load demands of large industrial bases and urban power centers. The transformer maintains stable temperature rise and low noise under prolonged full-load operation.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

35kV Oil-Immersed Renewable Energy Transformer Series – Full Specifications

35kV, 3-phase, 2-winding, oil-immersed, off-circuit tap-changer, renewable energy transformer, 35-38.5kV / 0.4-1.14kV, 1000-12500kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss (kW)Impedance
Voltage (%)
S22-M-1000/35-NX1100035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.60010.4006~14
S20-M-1000/35-NX2100035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.80010.4006~14
S18-M-1000/35-NX3100035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.90010.9006~14
S22-M-1250/35-NX1125035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.80012.5006~14
S20-M-1250/35-NX2125035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.90012.5006~14
S18-M-1250/35-NX3125035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.10013.2006~14
S22-M-1600/35-NX1160035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd110.90014.9006~14
S20-M-1600/35-NX2160035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.10014.9006~14
S18-M-1600/35-NX3160035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.30015.8006~14
S22-M-2000/35-NX1200035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.20016.5006~14
S20-M-2000/35-NX2200035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.40016.5006~14
S18-M-2000/35-NX3200035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.50017.4006~14
S22-M-2500/35-NX1250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.40017.6006~14
S20-M-2500/35-NX2250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.70017.6006~14
S18-M-2500/35-NX3250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.80019.6006~14
S22-M-3000/35-NX1300035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.60020.3006~14
S20-M-3000/35-NX2300035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.90020.3006~14
S18-M-3000/35-NX3300035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.10022.5006~14
S22-M-3150/35-NX1315035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd111.70020.7006~14
S20-M-3150/35-NX2315035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.00020.7006~14
S18-M-3150/35-NX3315035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.20023.0006~14
S22-M-4000/35-NX1400035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.00024.6006~14
S20-M-4000/35-NX2400035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.30024.6006~14
S18-M-4000/35-NX3400035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.60027.3006~14
S22-M-4500/35-NX1450035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.20027.1006~14
S20-M-4500/35-NX2450035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.60027.1006~14
S18-M-4500/35-NX3450035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.00030.1006~14
S22-M-5000/35-NX1500035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.40028.2006~14
S20-M-5000/35-NX2500035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.80028.2006~14
S18-M-5000/35-NX3500035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.20031.3006~14
S22-M-5500/35-NX1550035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.60030.3006~14
S20-M-5500/35-NX2550035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.00030.3006~14
S18-M-5500/35-NX3550035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.50033.6006~14
S22-M-6300/35-NX1630035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd112.90031.5006~14
S20-M-6300/35-NX2630035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.40031.5006~14
S18-M-6300/35-NX3630035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14Yd113.80035.0006~14
S22-M-8000/35-NX1800035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd114.00034.6006~14
S20-M-8000/35-NX2800035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd114.70034.6006~14
S18-M-8000/35-NX3800035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd115.20038.1006~14
S22-M-10000/35-NX11000035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd114.80040.8006~14
S20-M-10000/35-NX21000035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd115.70040.8006~14
S18-M-10000/35-NX31000035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd116.30045.3006~14
S22-M-12500/35-NX11250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd115.60050.7006~14
S20-M-12500/35-NX21250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd116.50050.7006~14
S18-M-12500/35-NX31250035, 38.5±2×2.5%0.4, 0.69, 0.8, 1.14YNd117.20056.3006~14
Note:
1.±2×2.5% is shown as the default tapping range in this table. Other tapping ranges (e.g., ±5%) are available upon request.
2.Other high and low voltages are available upon request.
3.Other vector groups are available upon request.
4.Efficiency classes (NX1/NX2/NX3) are in accordance with GB 20052-2024 for renewable energy transformers (PV, wind, energy storage) of 500kVA and above.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.