6kV, 3-phase, 2-winding, oil-immersed, off-circuit tap-changer, renewable energy transformer, 6-7.2kV / 0.4-1.14kV, 500-2000kVA | ||||||||
| Model | Rated Capacity (kVA) | HV (kV) | HV Tapping Range | LV (kV) | Vector Group | No-Load Loss (kW) | Load Loss (kW) | Impedance Voltage (%) |
| S22-M-500/6-NX1 | 500 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.385 | 3.900 | 4~8 |
| S20-M-500/6-NX2 | 500 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.430 | 4.330 | 4~8 |
| S18-M-500/6-NX3 | 500 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.480 | 5.410 | 4~8 |
| S22-M-630/6-NX1 | 630 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.460 | 4.460 | 4~8 |
| S20-M-630/6-NX2 | 630 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.510 | 4.960 | 4~8 |
| S18-M-630/6-NX3 | 630 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.570 | 6.200 | 4~8 |
| S22-M-800/6-NX1 | 800 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.560 | 5.400 | 4~8 |
| S20-M-800/6-NX2 | 800 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.630 | 6.000 | 4~8 |
| S18-M-800/6-NX3 | 800 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.700 | 7.500 | 4~8 |
| S22-M-1000/6-NX1 | 1000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.665 | 7.415 | 4~8 |
| S20-M-1000/6-NX2 | 1000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.745 | 8.240 | 4~8 |
| S18-M-1000/6-NX3 | 1000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.830 | 10.300 | 4~8 |
| S22-M-1250/6-NX1 | 1250 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.780 | 8.640 | 4~8 |
| S20-M-1250/6-NX2 | 1250 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.870 | 9.600 | 4~8 |
| S18-M-1250/6-NX3 | 1250 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.970 | 12.000 | 4~8 |
| S22-M-1600/6-NX1 | 1600 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 0.940 | 10.440 | 4~8 |
| S20-M-1600/6-NX2 | 1600 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 1.050 | 11.600 | 4~8 |
| S18-M-1600/6-NX3 | 1600 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 1.170 | 14.500 | 4~8 |
| S22-M-2000/6-NX1 | 2000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 1.085 | 13.180 | 4~8 |
| S20-M-2000/6-NX2 | 2000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 1.225 | 14.640 | 4~8 |
| S18-M-2000/6-NX3 | 2000 | 6, 6.3, 6.6, 7.2 | ±5% | 0.4, 0.69, 0.8, 1.14 | Dyn11 | 1.360 | 18.300 | 4~8 |
| Note: 1.±5% is shown as the default tapping range in this table. Other tapping ranges are available upon request. 2.Other high and low voltages are available upon request. 3.Other vector groups are available upon request. 4.Efficiency classes (NX1/NX2/NX3) are in accordance with GB 20052-2024 for renewable energy transformers (PV, wind, energy storage). 5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet. | ||||||||
* For specific product requests, please Contact Us for customized solutions to your needs.