S22-10000/35-NX1 Three-Phase Oil-Immersed Hermetically Sealed Power Transformer

35kV Oil-Immersed Power Transformer Series

S22-10000/35-NX1 Three-Phase Oil-Immersed Hermetically Sealed Power Transformer

The S22-10000/35-NX1 is a three-phase oil-immersed power transformer with a rated capacity of 10000kVA and a high-voltage side rating of 35kV. The transformer is designed with S22 loss level, achieving Class 1 energy efficiency (NX1) according to GB 20052-2024, with no-load loss significantly lower than conventional models. It features a robust oil-immersed structure with high reliability, low noise, and strong short-circuit withstand capability. The core is made of high-quality cold-rolled grain-oriented silicon steel, and windings use oxygen-free copper conductors. It is suitable for 35kV power systems, providing reliable and energy-efficient power supply for large industrial bases, commercial centers, urban power grids, and substations.
  • Rated Capacity: 10000 kVA
  • Rated Voltage Ratio: 35/10.5 kV
  • Connection Group: YNd11
  • Cooling Method: ONAN
  • Energy Efficiency Class: NX1
  • Standard:IEC 60076, GB/T 6451-2023, GB 20052-2024

Product Details

Learn more about our products

Product Model S22-10000/35-NX1
No-Load Loss ≤4.8 kW
Rated Capacity 10000 kVA
No-Load Current ≤0.32%
Phase 3-phase
Load Loss (75°C) ≤40.8 kW
Rated Voltage Ratio 35/10.5 kV
Short-Circuit Impedance 8.0%
HV Tapping Range ±2×2.5%
Temperature Rise Limit Top oil ≤55K, Winding ≤65K
Rated Frequency 50 Hz
Noise (Sound Pressure Level) ≤65 dB(A)
Connection Group YNd11 (Dyn11 available upon request)
Protection Degree IP54
Cooling Method ONAN
Standard IEC 60076, GB/T 6451-2023, GB 20052-2024
Insulation Class A, LI200 AC85 / AC5
Energy Efficiency Class NX1
01.

Core advantages

Class 1 Energy Efficiency (NX1)
Complies with GB 20052-2024 Class 1 energy efficiency standard. No-load loss is approximately 30% lower than S13 and 15% lower than S20, significantly reducing long-term operating costs.
High Reliability & Strong Short-Circuit Withstand
Oil-immersed structure with optimized core and winding design ensures stable operation under continuous heavy loads, with strong short-circuit resistance and long service life.
Low Noise & Wide Application
Optimized electromagnetic design delivers low noise operation, suitable for urban power grids, large industrial bases, and commercial centers where environmental requirements are strict.
02.

Application scenarios

No data was found
01.

Authoritative Certification

CE
Our transformers are CE certified, ensuring full compliance with EU safety, health, and environmental standards.
UL
Our transformers are UL certified, confirming they meet rigorous ANSI/IEEE safety standards for North American market entry.
ASTA
Our transformers have obtained ASTA type-test certification, verifying IEC 60076 compliance.
EAC
Our transformers are EAC certified, ensuring compliance with safety and EMC regulations for the Eurasian market.
SASO
We provide SASO-compliant transformers and assist clients in obtaining the Batch Certificate of Conformity (CoC) through the SABER platform.
02.

Quality Assurance

Partner Factory Audit
Regular on-site audits of partner factories to verify ISO, CE, and UL certifications.
Full-Process Quality Control
From raw material inspection to pre-shipment final inspection, every unit is checked against specifications.
Comprehensive Test Reports
Each transformer includes a detailed factory test report. 100% full inspection before dispatch.
Third-Party Inspection Support
SGS, BV, or other accredited third-party inspection available upon customer request.
01.

Technical Documents

No data was found
02.

Certification Materials

No data was found

35kV Oil-Immersed Power Transformer Series – Full Specifications

35kV, 3-phase, 2-winding, oil-immersed, off-circuit tap-changer, power transformer, 630-31500kVA

ModelRated Capacity
(kVA)
HV (kV)HV Tapping
Range
LV (kV)Vector GroupNo-Load Loss
(kW)
Load Loss
(75°C) (kW)
Impedance
Voltage (%)
S22-M-630/3563035±2×2.5%3.15,6.3,10.5Yd110.4627.0976.5
S20-M-630/3563035±2×2.5%3.15,6.3,10.5Yd110.5287.0976.5
S18-M-630/3563035±2×2.5%3.15,6.3,10.5Yd110.6607.4706.5
S22-M-800/3580035±2×2.5%3.15,6.3,10.5Yd110.5468.4846.5
S20-M-800/3580035±2×2.5%3.15,6.3,10.5Yd110.6248.4846.5
S18-M-800/3580035±2×2.5%3.15,6.3,10.5Yd110.7808.9306.5
S22-M-1000/35100035±2×2.5%3.15,6.3,10.5Yd110.64410.3556.5
S20-M-1000/35100035±2×2.5%3.15,6.3,10.5Yd110.73610.3556.5
S18-M-1000/35100035±2×2.5%3.15,6.3,10.5Yd110.92010.9006.5
S22-M-1250/35125035±2×2.5%3.15,6.3,10.5Yd110.78412.5406.5
S20-M-1250/35125035±2×2.5%3.15,6.3,10.5Yd110.89612.5406.5
S18-M-1250/35125035±2×2.5%3.15,6.3,10.5Yd111.12013.2006.5
S22-M-1600/35160035±2×2.5%3.15,6.3,10.5Yd110.94515.0106.5
S20-M-1600/35160035±2×2.5%3.15,6.3,10.5Yd111.08015.0106.5
S18-M-1600/35160035±2×2.5%3.15,6.3,10.5Yd111.35015.8006.5
S22-M-2000/35200035±2×2.5%3.15,6.3,10.5Yd111.21816.5306.5
S20-M-2000/35200035±2×2.5%3.15,6.3,10.5Yd111.39216.5306.5
S18-M-2000/35200035±2×2.5%3.15,6.3,10.5Yd111.74017.4006.5
S22-M-2500/35250035±2×2.5%3.15,6.3,10.5Yd111.43517.6706.5
S20-M-2500/35250035±2×2.5%3.15,6.3,10.5Yd111.64017.6706.5
S18-M-2500/35250035±2×2.5%3.15,6.3,10.5Yd112.05018.6006.5
S22-M-3150/35-NX1315035,38.5±2×2.5%3.15,6.3,10.5Yd111.70020.7007.0
S20-M-3150/35-NX2315035,38.5±2×2.5%3.15,6.3,10.5Yd112.00020.7007.0
S18-M-3150/35-NX3315035,38.5±2×2.5%3.15,6.3,10.5Yd112.40021.9007.0
S22-4000/35-NX1400035,38.5±2×2.5%3.15,6.3,10.5Yd112.00024.6007.0
S20-4000/35-NX2400035,38.5±2×2.5%3.15,6.3,10.5Yd112.30024.6007.0
S18-4000/35-NX3400035,38.5±2×2.5%3.15,6.3,10.5Yd112.90025.9007.0
S22-5000/35-NX1500035,38.5±2×2.5%3.15,6.3,10.5Yd112.40028.2007.0
S20-5000/35-NX2500035,38.5±2×2.5%3.15,6.3,10.5Yd112.80028.2007.0
S18-5000/35-NX3500035,38.5±2×2.5%3.15,6.3,10.5Yd113.50029.7007.0
S22-6300/35-NX1630035,38.5±2×2.5%3.15,6.3,10.5Yd112.90031.5008.0
S20-6300/35-NX2630035,38.5±2×2.5%3.15,6.3,10.5Yd113.40031.5008.0
S18-6300/35-NX3630035,38.5±2×2.5%3.15,6.3,10.5Yd114.20033.3008.0
S22-8000/35-NX1800035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd114.00034.6008.0
S20-8000/35-NX2800035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd114.70034.6008.0
S18-8000/35-NX3800035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd115.80036.5008.0
S22-10000/35-NX11000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd114.80040.8008.0
S20-10000/35-NX21000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd115.70040.8008.0
S18-10000/35-NX31000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd117.00043.0008.0
S22-12500/35-NX11250035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd115.50048.4008.0
S20-12500/35-NX21250035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd116.50048.4008.0
S18-12500/35-NX31250035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd118.00051.1008.0
S22-16000/35-NX11600035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd116.70059.2008.0
S20-16000/35-NX21600035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd117.90059.2008.0
S18-16000/35-NX31600035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd119.70062.5008.0
S22-20000/35-NX12000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd117.90071.6008.0
S20-20000/35-NX22000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd119.40071.6008.0
S18-20000/35-NX32000035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1111.50075.5008.0
S22-25000/35-NX12500035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd119.40084.60010.0
S20-25000/35-NX22500035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1111.10084.60010.0
S18-25000/35-NX32500035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1113.60089.30010.0
S22-31500/35-NX13150035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1111.100100.80010.0
S20-31500/35-NX23150035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1113.100100.80010.0
S18-31500/35-NX33150035,38.5±2×2.5%3.15,3.3,6.3,6.6,10.5YNd1116.200106.40010.0
Note:
1.±2×2.5% is shown as the default tapping range in this table. Other tapping ranges are available upon request.
2.Other high and low voltages are available upon request.
3.Vector group options: Yd11 or YNd11 as listed in the table. Other vector groups are available upon request.
4.Efficiency classes (NX1/NX2/NX3) apply to 3150kVA and above, in accordance with GB 20052-2024.
5.For IEC, ANSI, or other standards, or special frequency requirements, please contact us for a customized datasheet.